11
Standard Object Types Supported
Object Type
Supported
Objects
Dynamically
Creatable
Dynamically
Deletable
Optional
Properties
Supported
Writable
Properties
Analog Input
;
Reliability Out_of_Service
Analog Value ; Reliability
Present_Value
a
Out_of_Service
a
Object_Name
b
Binary Input ;
Reliability
Active_Text
Inactive_Text
Out_of_Service
Binary Value ;
Reliability
Active_Text
Inactive_Text
Present_Value
Out_of_Service
Device ;
Max_Master
Max_Info_frames
Object_Identifier
Object_name
Max_Master
Group
;
N/A N/A
Multi-state Value ;
Reliability
States_Text
Present_Value
Out_of_Service
Schedule ; Weekly_schedule
Present_Value
Weekly_Schedule
a: The following AV’s are defined as read only. When Out_of_Service properties is set to true, the Present_Value if
written is not derived to the application level of the thermostat.
¾ Room Humidity (AV11)
¾ PI Heating Demand (AV20)
¾ PI Cooling Demand (AV21)
¾ Economizer Output (AV22)
¾ Eff Reset Humidification RH Spt (AV96)
¾ Humidifier Output (AV101)
b: Object_Name property is writable for 1 object only :
¾ Room_Temperature (AV7)
List of Proprietary Properties
Property name ID BACnet Data type Description
Major_Version 1000 CharacterString
The version number of the BACnet
communications module. This the hardware
version number
MS/TP_Address 1001 Unsigned Display the MAC layer address of the module
MS/TP_Baud_Rate 1002 Unsigned
Display the communication baud rate of the
module
Sensor_Offset 1005 REAL
Display the temperature or humidity calibration
value. The range is –5.0 deg F to 5.0 deg F for a
temperature and –15% to 15% for humidity.